1666
19 CC-LINK INSTRUCTIONS
19.7 Setting Network Parameters
After completion of the G(P).RLPASET instruction, turn on SB0003, a refresh instruction that is used for parameter change
with the dedicated instruction, to start the cyclic data refresh.
Precautions
Two or more G(P).RLPASET instructions cannot be executed concurrently.
The G(P).RLPASET instruction is not available in a system containing a standby master station.
Do not set network parameters using the engineering tool for modules for which network parameters are set using the
G(P).RLPASET instruction. If the G(P).RLPASET instruction is executed for a module for which network parameters are set
using the engineering tool, the instruction will be terminated with an error and the network parameter settings are not
reflected.
Stop the data link using "Data Link Stop" (SB0002) before executing the G(P).RLPASET instruction.
Operation error
If no stations are faulty
If all stations are faulty
Error code
((s1)+0)
Description
B000H to BFFFH MELSEC iQ-R CC-Link System Master/Local Module User's Manual (Application)
ON
ON
OFF
OFF
END END END END END END END 0000000
Sequence scan
Data link stop
Own station data link status
(X01)
Refresh instruction when changing
parameters by the dedicated
instruction (SB0003)
Data link stop
(SB0002)
Data link stop completion
(SB0045)
G(P).PLPASET instruction
Completion device (d)
Completion status
indication device (d)+1
Refresh stop
Data link start
Refresh start
Completion of
the instruction
Completed with an error
1 scan
Completed successfully
END END END END END END END 0000000
ON
ON
OFF
OFF
Sequence scan
Data link stop
Own station data link status
(X01)
Data link stop
(SB0002)
Data link stop completion
(SB0045)
G(P).PLPASET instruction
Completion device (d)
Completion status
indication device (d)+1
Refresh stop
Return processing
Completion of
the instruction
Refresh start
Completed with an error
Modules
return
to the system.
1 scan
Completed successfully
Data link start
Refresh instruction when changing
parameters by the dedicated
instruction (SB0003)