19 CC-LINK INSTRUCTIONS
19.8 Performing a Message Transmission to a Remote Device Station
1669
19
Processing details
These instructions performs a message transmission to a remote device station.
The instructions can be executed to a remote device station, for example NZ2AW1C2AL, that supports the message
transmission function.
The following figure shows how the G(P).RDMSG instruction operates during execution.
The completion status of the G(P).RDMSG instruction can be checked with the completion device (d2) and the completion
status indication device (d2)+1.
The send data specified by (s2) is stored to the master station for the size specified by (s1)+2.
The master station sends data to the target station specified by (s1)+1.
Processing is performed for the data in the target station.
The master station receives a processing result from the target station.
The master station stores data in the device specified by (d1) and later, and the device specified by (d2) turns on.
Completion device (d2)
This device turns on during END processing of the scan where the G(P).RDMSG instruction completes, and turns off during the next END processing.
Completion status indication device (d2)+1
This device turns on or off depending on the completion status of the G(P).RDMSG instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the G(P).RDMSG instruction completes, and turns off during the
next END processing.
G(P).RDMSG
(s2)
(d1)
Ô
Ó
Õ
Ò
Ö
CPU module CC-Link master station
[Own station] [Target station]
Response message
Request message
Receive data
Send data
CC-Link remote device station
END0 0 END0ENDEND 0 END0
OFF
OFF
OFF
OFF
ON
ON
Sequence scan
G(P).RDMSG instruction
Completion device (d2)
1 scan
Completion of
the instruction
Completed successfully
Execution of the instruction
Completion status
indication device (d2)+1
Completed with an error