1678
20 SERIAL COMMUNICATION INSTRUCTIONS
20.2 Executing the Protocols Registered for the Predefined Protocol Support Function
Applicable devices
*1 Index modification is not available.
*2 FX and FY cannot be used.
*3 FD cannot be used.
Control data
*1 If the nth protocol caused an error during its execution while two or more protocols are being executed, none of the subsequent
protocols will be executed.
*2 For details on the special protocols, refer to the following.
Page 1680 Special protocol
Operand Bit Word Double word Indirect
specification
Constant Others
(U)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(U)
*1

(n1) 
*3

(n2) 
*3

(s) 
*3

(d)
*2

*3

Operand: (s)
Device Item Description Setting range Set by
+0 Execution result Used to store the execution result of the G(P).CPRTCL instruction. If two or more
protocols are executed, the execution result of the last protocol will be stored.
*1
•0: Normal
Other than 0: Error (error code)
System
+1 Resulting number of
executed protocols
Used to store the number of actually executed protocols.
Also for the protocols that caused an error, the execution result of the last protocol
will be stored.
If an error is included in the setting data or the control data setting details, "0" will be
stored.
1 to 8 System
+2 Execution protocol
number specification
Sets the number of the first protocol or special protocol to be executed.
*2
1 to 128, 201 to
207
User

+9 Sets the number of the eighth protocol or special protocol to be executed.
*2
+10 Matched receive packet
number
Used to store the matched receive packet number if the communication type of the
first protocol executed is "Send only" or "Send and receive".
If the first protocol caused an error during its execution, "0" will be stored.
If a special protocol is executed, "0" will be stored.
*2
0, 1 to 16 System

+17 Used to store the matched receive packet number if the communication type of the
eighth protocol executed is "Send only" or "Send and receive".
If the eighth protocol caused an error during its execution, "0" will be stored.
If a special protocol is executed, "0" will be stored.
*2