20 SERIAL COMMUNICATION INSTRUCTIONS
20.11 Registering/Canceling the Programmable Controller CPU Monitoring
1707
20
When programmable controller CPU monitoring is canceled
+14,
+15
1st piece (1st
block)
Start device monitored Specifies the start device monitored of this block. 0 or more User
+16 Number of registered
points
Specifies the number of registered, or read, points of this block. For a bit
device, specify the number of points in units of words.
0: Device not monitored
1 or more: Number of registered points
0 or more User
+17 Sending
upon
condition
matching
Monitoring
condition
Specifies the monitoring condition for this block.
0: Not specified (when sending with a fixed cycle)
1 or more: Monitoring conditions
Refer to the
following.
MELSEC
iQ-R Serial
Communication
Module User's
Manual
(Application)
User
+18 Monitoring
condition
value
Specifies the monitoring condition value for this block. Specify 0 for
sending with a fixed cycle.
0 or more: Monitoring conditions
User
+19 User
frame
output
start
pointer
Specifies the start pointer of the table where the user frame numbers for
sending upon condition matching have been set.
0: Not specified (when sending with a fixed cycle)
1 to 100: Start pointer
0, 1 to 100 User
+20 Number of
user
frames
sent
Specifies the number of user frames that are sent, or output, upon
condition matching.
0: Not specified (when sending with a fixed cycle)
1 to 100: Amount of data sent
0, 1 to 100 User
+21 For system Use prohibited 
+22 to
+102
2nd to 10th piece of programmable
controller CPU monitoring setting (2nd to
10th block)
Same row as 1st piece of programmable controller CPU monitoring
setting
User
+103 CPU status
monitoring
setting
(error
monitoring 11th
piece)
(11th block)
Sending
upon
condition
matching
Fixed
value
Specifies the fixed value if the CPU status is monitored. 1 User
+104 0 User
+105 0 User
+106 1 User
+107 5 User
+108 1 User
+109 User
frame
output
start
pointer
Specifies the start pointer of the table where the user frame numbers for
sending upon condition matching have been set.
0: Not specified (when sending with a fixed cycle)
1 to 100: Start pointer
0, 1 to 100 User
+110 Number of
user
frames
sent
Specifies the number of user frames that are sent, or output, upon
condition matching.
0: Not specified (when sending with a fixed cycle)
1 to 100: Amount of data sent
0, 1 to 100 User
+1
11 For system Use prohibited 
Operand: (s2)
Device Item Description Setting range Set by
+0 Execution type Specifies "0." 0 User
+1 Completion status Used to store the completion status.
•0: Normal
Other than 0: Error (error code)
System
+2 Request type Specifies the contents of request.
3: Cancels programmable controller CPU monitoring.
3 User
+3 to
+111
For system Use prohibited (not available also for other applications such as programming) System
Operand: (s2)
Device Item Description Setting range Set by