20 SERIAL COMMUNICATION INSTRUCTIONS
20.11 Registering/Canceling the Programmable Controller CPU Monitoring
Applicable devices
*1 Index modification is not available.
*2 FX and FY cannot be used.
*3 FD cannot be used.
Control data
When programmable controller CPU monitoring is registered
Operand Bit Word Double word Indirect
specification
Constant Others
(U)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(U)
*1

(s1)
*2

*3
 
(s2) 
*3
 
(d1) 
*3
 
(d2)
*2

*3
 
Operand: (s2)
Device Item Description Setting range Set by
+0 Execution type Specifies 0. 0 User
+1 Completion status Used to store the completion status.
•0: Normal
Other than 0: Error (error code)
System
+2 Request type Specifies the contents of request.
2: Performs programmable controller CPU monitoring registration.
2 User
+3 Unit of cycle time Specifies the unit of the cycle time.
0: 100ms
1: Second
2: Minute
0 to 2 User
+4 Cycle time Specifies the cycle time. 1H to FFFFH User
+5 Programmable controller CPU monitoring
function
Specifies the monitoring function.
1: Sending with a fixed cycle
2: Sending upon condition matching
1, 2 User
+6 Sending means for programmable
controller CPU monitoring
Specifies the sending means.
0: Sending data (device data, CPU error information)
0 User
+7 Cyclic
broadcast send
User frame output start
pointer
Specifies the start pointer of the table where the user frame numbers for
sending with a fixed cycle have been set.
0: Not specified (sending upon condition matching)
1 to 100: Amount of data sent
0, 1 to 100 User
+8 Number of user frames
sent
Specifies the number of user frames that are sent, or output, with a fixed
cycle.
0: Not specified (sending upon condition matching)
1 to 100: Amount of data sent
0, 1 to 100 User
+9 For system Use prohibited 
+10 Number of reserved word blocks Specifies the number of blocks of the word device to be monitored. 0 to 10 User
+11 Number of registered bit blocks Specifies the number of blocks of the bit device to be monitored. 0 to 10 User
+12 Programmable controller CPU error
monitoring (programmable controller
CPU status monitoring)
Specifies whether to monitor programmable controller CPU errors.
0: Not monitored
1: Monitored
0, 1 User
+13 Programmable
controller CPU
monitoring
setting
Device code Specifies the code of the device to be monitored.
0: Not monitored
Other than 0: Monitored (code of the device to be monitored)
0 or more User