EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 1790

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1788
24 C INTELLIGENT FUNCTION MODULE INSTRUCTIONS
24.1 User Function Execution Instruction
Applicable devices
*1 Index modification is not available.
*2 FX and FY cannot be used.
*3 FD cannot be used.
*4 T, ST, C, and FD cannot be used.
Control data
Request data
Response data
Operand Bit Word Double word Indirect
specification
Constant Others
(U)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(U)
*1
 
(s1) 
*3

(s2) 
*3

(d1) 
*3

(d2)
*2

*4

Operand: (s1)
Device Item Description Setting range Set by
+0 Allowable amount of
response data
Sets the allowable number of words of response data that can be stored in (d1). 1 to 8192 User
+1 Completion status The completion status is stored upon completion of the instruction.
0: Completed successfully
Other than 0: Completed with an error (error code)
System
Operand: (s2)
Device Item Description Setting range Set by
+0 Request data length Specify the request data length. (Number of words) 1 to 8192 User
+1 to + Request data Specify the request data. User
Operand: (d1)
Device Item Description Setting range Set by
+0 Response data length Response data length is stored. (Number of words) 0 to 8192 System
+1 to + Response data Response data is stored. System

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series

Related product manuals