EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 1954

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1952
32 STRING FUNCTIONS
32.4 Concatenating String Data
Operation result
1. Function without EN/ENO
The operation processing is performed. The operation result is output from (d).
2. Function with EN/ENO
The execution conditions and operation results will be as follows.
*1 If the value FALSE is output from ENO, the output data from (d) will be undefined. Create a program so that the undefined value will not
be used in operations.
Operation error
Execution condition Operation result
EN ENO (d)
TRUE (executed) TRUE Operation result output value
FALSE (not executed) FALSE
*1
Undefined value
Error code
(SD0)
Description
2820H There is no NULL code (00H) in each setting area specified by (s1) to (s28) in the device/label memory.
There is no NULL code (00H) in each setting area in the device/label memory in the device specified by (d) and later.
2821H The device numbers are overlapping between (s1) to (s28) and (d).
3405H The number of characters in the strings input to (s1) to (s28) exceeds 16383.
The number of characters in the strings input to (s1) to (s28) is 0.
The number of characters of the character string in the device specified by (d) exceeds 16383.
3406H The entire string after concatenate processing cannot be stored in the setting area specified by (d) in the device/label memory. (The
number of required points is insufficient.)