36 COUNTER/TIMER FUNCTION BLOCKS
36.8 Timer Function Block
1999
36
[Timing chart]
TIMER_LOW_FB_M
This is a low-speed timer whose unit of measurement is 1 to 1000ms. When (s1) turns on, measurement of the current
value starts. The measurement starts from (s3)1 to 1000ms (variable; set in parameter). When the value reaches (s2)1 to
1000ms, (d2) turns on. The measured current value is output to (d1).
When (s1) turns off, the current value returns to the initial value (s3), and (s2) also turns off.
The unit of measurement of the low-speed timer is 100ms by default. The unit can be changed in the range from 1 to
1000ms (in increments of 1ms).
The valid setting range of (s2) is 0 to 32767.
The valid setting range of (s3) is -32768 to 32767. Note that if a negative value is specified, 0 will be used as the initial
value.
Ex.
[Ladder example]
[Timing chart]
1
ON
90ms
10
M10
M0
OFF
OFF
D10
M0 Coil
10 ValueOutPreset
1 StatusValueIn M10
D10
TIMER_LOW_FB_M
1
ON
900ms
10
M10
M0
OFF
OFF
D10