36 COUNTER/TIMER FUNCTION BLOCKS
36.8 Timer Function Block
TIMER_CONT_FB_M/TIMER_CONTHFB_M
This is a retentive timer that measures the on time of a variable. When (s1) turns on, measurement of the current value
starts. There are two retentive timers: low-speed (TIMER_CONT_FB_M) and high-speed (TIMER_CONTHFB_M) retentive
timers.
The measurement starts from (s3)1 to 1000ms (0.1 to 100ms for the high-speed retentive timer) (variable; set in
parameter). When the value reaches (s2)1 to 1000ms (0.1 to 100ms for the high-speed retentive timer), (d2) turns on. The
measured current value is output to (d1).
Even when (s1) is off, the on/off states of (d1) and (d2) are held. When (s1) turns on again, the measurement resumes with
the measured value that has been held.
The unit of measurement (time limit) for the retentive timers is common to both the low-speed timer (TIMER_LOW_FB_M)
and high-speed timer (TIMER_HIGH_FB_M).
The valid setting range of (s2) is 0 to 32767.
The valid setting range of (s3) is -32768 to 32767. Note that if a negative value is specified, 0 will be used as the initial
value.
To reset (d1) of a retentive timer, reset (s1) of FB directly.
Ex.
Label name: TIMER_CONT_FB_M_1
[Ladder program]
[ST program]
RST(M0,TIMER_CONT_FB_M_1.Coil)
[Ladder example]
[Timing chart]
Operation error
There is no operation error.
Low-speed retentive timer: Low-speed timer
High-speed retentive timer: High-speed timer
M0 ENO
d
EN
RST
TIMER_CONT_FB_M_1.Coil
X0 Coil
200 ValueOutPreset
0 StatusValueIn M10
D10
TIMER_CONT_FB_M
01
ON
ON
150
M10
X0
OFF
OFF
151 200
5s15s
D10
... ...