5 - 14
5. ETHERNET CONNECTION
5.3 GOT Side Settings
5.3 GOT Side Settings
5.3.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
1. Select [Common] [Controller Setting] from the
menu.
2. The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3. Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller
Type to be connected.
• @@@
• Driver:
Ethernet(MELSEC), Q17nNC, CRnD-700, Gateway
Ethernet(FX), Gateway
4. The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
5.3.2 Communication detail settings
Click the [OK] button when settings are completed.
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
5.3.2 Communication detail settings
Make the settings according to the usage environment.
*1 To connect the GOT with the Ethernet module (Q Series) in
the one-on-one relationship using a cross cable, set
[Timeout Time] to 6sec. or longer.
Item Description Range
GOT Net No.
Set the network No. of the GOT.
(Default: 1)
1 to 239
GOT Station
Set the station No. of the GOT.
(Default: 1)
1 to 64
GOT Ethernet
Setting
Set the GOT IP address, subnet mask,
default gateway, peripheral S/W
communication port No., transparent
port No.
5.3.3GOT Ethernet
setting
GOT
Communication
Port No.
Set the GOT port No. for the
connection with the Ethernet module.
• For Ethernet (MELSEC), Q17nNC,
and CRnD-700
(Default: 5001)
• For Ethernet(FX), Gateway
(Default: 5019)
1024 to 5010,
5014 to 65534
(Except for 5011 to
5013 and 49153)
Retry
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
0 to 5times
Startup Time
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
3 to 255sec
Timeout Time
*1
Set the time period for a
communication to time out.
(Default: 3sec)
1 to 90sec
Delay Time
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
0 to 10000
( 10ms)