6 - 10
6. DIRECT CONNECTION TO CPU
6.2 System Configuration
6.2.5 Connecting to FXCPU
When connecting to FX0, FX0S, FX0N, FX1, FX2 or FX2C
*1 For details of the GOT multi-drop connection, refer to the following.
18. GOT MULTI-DROP CONNECTION
*2 When using function expansion boards or function adapters, confirm the communication settings.
6.5 Precautions Connection to FXCPU (2)When connecting with function extension board or communication special
adapter
FXCPU
Function
expansion
board
Function
adapter
GOT
Connection cable
MELSEC-FX
Communication driver
PLC Connection cable GOT
Number of
connectable
equipment
Model
name
Function
expansion
board
*2
Function
adapter
*2
Communi
cation
type
Cable model
Max.
distance
Option device Model
FX
0
FX0S
FX0N
- - RS-422
GT01-C10R4-8P(1m)
GT01-C30R4-8P(3m)
GT01-C100R4-8P(10m)
GT01-C200R4-8P(20m)
GT01-C300R4-8P(30m)
30m
- (Built into GOT)
1 GOT for 1
PLC
GT15-RS4-9S
GT01-RS4-M
*1
-
FX
1
FX2
FX2C
- - RS-422
GT01-C30R4-25P(3m)
GT01-C100R4-25P(10m)
GT01-C200R4-25P(20m)
GT01-C300R4-25P(30m)
30m
- (Built into GOT)
GT15-RS4-9S
GT01-RS4-M
*1
-