12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
12 - 15
CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12
Parameter setting (when connecting to C
Controller module)
Use SW3PVC-CCPU-E Ver.3.05F or later for the CC-
Link utility.
(1) Connection settings
: Necessary : As necessary : Not necessary
*1 If the IP address of the C Controller module has been
changed, input the changed IP address or host name.
*2 If the account of the C Controller module has been changed,
input the changed user name and password.
(2) CC-Link Utility's [Parameter Settings]
(a) Parameter settings
: Necessary : As necessary : Not necessary
*1 When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 1 mode)], [Remote station points] cannot be set.
*2 Set the same number of occupied stations as that on the
GOT.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the C Controller
module, either turn the C Controller module OFF and
then ON or reset it.
Item Set value
Setting
necessity at
GOT connection
Target module
*1
192.168.3.3 (Default)
Write authority Mark the checkbox
User name
*2
target
Password
*2
password
Detailed settings -
Item
*1
Set value
Setting
necessity at
GOT
connection
Number of modules 1
Target module 1
Start I/O No. 0000
H
Channel No. (Use default value)
Operation settings
Type Master station (fixed)
Mode
Remote net
(Ver.1 mode)
Expanded cyclic setting Single
Occupied number Exclusive station 1
Error event: input data
status
Clear
CPU stop: data link status Refresh
Other settings (Use default value)
Station information settings
All connect count 1
Station Type
Sta.
No.1
Intelligent device
station
Occupied number
*2
Sta.
No.1
Exclusive station 1
Reserve/invalid
station select
Sta.
No.1
No setting
Intelligent buffer select
(word)
(Use default value)

Table of Contents

Other manuals for Mitsubishi GOT2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GOT2000 Series and is the answer not in the manual?

Mitsubishi GOT2000 Series Specifications

General IconGeneral
Power Supply24VDC
SoftwareGT Works3
ProcessorRISC CPU
InterfaceEthernet, USB, RS-232, RS-422/485
Operating Temperature0°C to 50°C
Display TypeTFT LCD
Storage Temperature-20°C to 60°C
Humidity10% to 90% (non-condensing)
Shock Resistance147 m/s² (15G), 11ms duration
Touch PanelAnalog Resistive