Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
102 6SE6400-5BB00-0BP0
P0821 BI: DDS bit 1 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4095:0
Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter
P0820).
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Note:
P0820 is also relevant for drive data set (DDS) selection.
3.14 BICO command parameters
P0840[3] BI: ON/OFF1 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 722:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Allows ON/OFF1 command source to be selected using BICO.
The first three digits describe the parameter number of the command source; the last digit denotes the bit
setting for that parameter. The default setting (ON right) is digital input 1 (722.0). Alternative source possible
only when function of digital input 1 is changed (via P0701) before changing value of P0840.
f
t
f max
(P1082)
f
2
0
P1082
f
P1121
t
2
1OFF,down
â‹…=
P2167
P1121
t
down,OFF1
OFF1
P2168
ON
P1120
r0052 Bit02
Operation
Pulse
cancellation
t
t
P2168
f
act ,motor
f
act ,inverter
Index:
P0840[0] : 1st. Command data set (CDS)
P0840[1] : 2nd. Command data set (CDS)
P0840[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0 = ON/OFF1 via BOP
Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).
Note:
- OFF1 means a ramp stop down to 0 using P1121.
- OFF1 is low active.
- For the priority of all soft commands, the following applies: OFF2, OFF3, OFF1