P1825  On-state voltage of IGBT Min: 0.0 
CStat:  CUT  Datatype: Float Unit: V  Def:  1.4 
P-Group:  INVERTER  Active: Immediately  QuickComm.: No  Max:  20.0 
Corrects on-state voltage of the IGBTs. 
P1828  Gating unit dead time Min: 0.00 
CStat:  CUT  Datatype: Float Unit: us  Def:  0.50 
P-Group:  INVERTER  Active: first confirm  QuickComm.: No  Max:  3.50 
Sets compensation time of gating unit interlock. 
 
3.31  Motor data identification 
P1909[3]  Ctrl. word of motor data ident. Min: 0 
CStat:  CUT  Datatype: U16 Unit: -  Def:  1 
P-Group:  CONTROL  Active: first confirm  QuickComm.: No  Max:  1 
Control word of motor data identification. 
Bitfields: 
Bit00   Estimation of Xs                           0  NO         1  YES 
Index: 
P1909[0]  :  1st. Drive data set (DDS) 
P1909[1]  :  2nd. Drive data set (DDS) 
P1909[2]  :  3rd. Drive data set (DDS) 
P1910  Select motor data identification Min: 0 
CStat:  CT  Datatype: U16 Unit: -  Def:  0 
P-Group:  MOTOR  Active: first confirm  QuickComm.: Yes  Max:  20 
Performs a motor data identification. 
Possible Settings: 
0 Disabled 
1  Identification of all parameters with parameter change 
2  Identification of all parameters without parameter change 
3  Identification of saturation curve with parameter change 
4  Identification of saturation curve without parameter change 
5  Identification of XsigDyn (r1920) without parameter change 
6  Identification of Tdead (r1926) without parameter change 
7  Identification of Rs (r1912 ) without parameter change 
8  Identification of Xs (r1915) without parameter change 
9  Identification of Tr (r1913) without parameter change 
10  Identification of Xsigma (r1914) without parameter change 
20  Set voltage vector 
Common Settings: 
P1910 = 1: 
  All motor data and inverter characteristic will be identified and parameter will be changed. 
-  P0350  stator resistance, 
-  P0354  rotor resistance, 
-  P0356  stator leakage inductance, 
-  P0358  rotor leakage inductance, 
-  P0360  main inductance 
-  P1825  on-state voltage of IGBTs 
-  P1828  compensation time of gating unit interlock 
 
P1910 = 3: 
  Saturation curve will be identified and parameter will be changed. 
-  P0362 ... P0365 magnetizing curve flux 1 .. 4 
-  P0366 ... P0369 magnetizing curve imag 1 .. 4 
Caution: 
Motor identification should normally be performed on a cold motor. However, the identification of the motor 
data should only be performed if the motor temperature is within 5°C of the measured ambient temperature 
stored in P0625. If the motor identification is not within the 5ºC limit then the correct functioning of Vector 
Control (VC, SLVC) cannot be guaranteed. This may cause instabilities when using vector control. 
 
The motor rating plate information with respect to the connection of the motor windings (Star or delta 
connection) must  be correct in order to establish the correct equivalent circuit data. The motor identification 
calculates this data based on a Phase of a Star equivalent circuit P0350 - P0360, irrespective of whether 
the motor is connected star or delta. This must be considered when the motor data is input directly. 
Note: 
-  In order to that the motor identification routine supplies the correct data, before selecting, fast 
commissioning should be carried-out. 
-  If the motor data identification routine is activated (e.g. P1910 = 1), then at the next ON command, the 
measuring operation is started and alarm A0541 is generated. After the measurement is completed, 
both P1910 and the alarm are reset. 