EasyManuals Logo

Siemens MICROMASTER 440 Parameter Guide

Siemens MICROMASTER 440
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
52 6SE6400-5BB00-0BP0
NEMA Motor
T
1
T
4
T
7
T
3
T
6
T
9
T
8
T
5
T
2
Volts
UVW
T
1
-T
7
T
2
-T
8
T
3
-T
9
low
T
4
-T
5
-T
6
T
1
T
2
T
3
high
Connected
together
Connection
T
1
-T
7
T
2
-T
8
T
3
-T
9
Y Y
Y
UVW
T
1
-T
6
-T
7
T
2
-T
4
-T
8
T
3
-T
5
-T
9
-
T
1
T
2
T
3
T
4
-T
7
T
5
-T
8
T
6
-T
9
∆ ∆
T
1
T
4
T
7
T
2
T
5
T
8
T
3
T
9
T
6
e.g.: Volts 230 V YY (low) / 460 V Y (high)
Volts
low
high
Connected
together
Connection
P0305[3] Rated motor current Min: 0.01
CStat: C Datatype: Float Unit: A Def: 3.25
P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 10000.00
Nominal motor current [A] from rating plate - see diagram in P0304.
Index:
P0305[0] : 1st. Drive data set (DDS)
P0305[1] : 2nd. Drive data set (DDS)
P0305[2] : 3rd. Drive data set (DDS)
Dependency:
- Changeable only when P0010 = 1 (quick commissioning).
- Default value is depending on inverter type and its rating data.
- Depends also on P0320 (motor magnetization current).
Note:
The maximum value of P0305 depends on the maximum inverter current r0209 and the motor type:
Synchronous motor :
r0209 2 = P0305
syn max,
Asynchronous motor :
r0209 = P0305
asyn max,
It is recommanded that the ratio of P0305 (rated motor current) and r0207 (rated inverter current) should not
be lower than:
U/f :
SLVC and VC :
r0207
P0305
8
1
r0207
P0305
4
1
P0307[3] Rated motor power Min: 0.01
CStat: C Datatype: Float Unit: - Def: 0.12
P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 2000.00
Nominal motor power [kW/hp] from rating plate.
Index:
P0307[0] : 1st. Drive data set (DDS)
P0307[1] : 2nd. Drive data set (DDS)
P0307[2] : 3rd. Drive data set (DDS)
Dependency:
- If P0100 = 1, values will be in [hp] - see diagram P0304 (rating plate).
- Changeable only when P0010 = 1 (quick commissioning).
- Default value is depending on inverter type and its rating data.
Level
1
Level
1
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens MICROMASTER 440

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MICROMASTER 440 and is the answer not in the manual?

Siemens MICROMASTER 440 Specifications

General IconGeneral
Power Range0.12 kW to 250 kW
Output Voltage0 V to Input Voltage
Output Frequency0 Hz to 650 Hz
Control ModesVector control
Overload Capability150% for 60 seconds
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesPROFIBUS, DeviceNet, CANopen, Modbus RTU
Enclosure RatingIP20
Ambient Temperature-10°C to +50°C
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)

Related product manuals