Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
114 6SE6400-5BB00-0BP0
Direct selection of FF P1001 via DIN 1:
P
1
0
1
6
P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1
DIN1
r1024
r0722.0
P1020
1
2,3
P1001
0
0
P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1
P
1
0
1
7
DIN2 r0722.1
P1021
1
2,3
P1002
0
0
. . . .
+
. . .
+
Dependency:
Select fixed frequency operation (using P1000).
Inverter requires ON command to start in the case of direct selection (P0701 - P0706 = 15).
Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002[3] Fixed frequency 2 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 5.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 2.
Index:
P1002[0] : 1st. Drive data set (DDS)
P1002[1] : 2nd. Drive data set (DDS)
P1002[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1003[3] Fixed frequency 3 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 10.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 3.
Index:
P1003[0] : 1st. Drive data set (DDS)
P1003[1] : 2nd. Drive data set (DDS)
P1003[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1004[3] Fixed frequency 4 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 15.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 4.
Index:
P1004[0] : 1st. Drive data set (DDS)
P1004[1] : 2nd. Drive data set (DDS)
P1004[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1005[3] Fixed frequency 5 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 20.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 5.
Index:
P1005[0] : 1st. Drive data set (DDS)
P1005[1] : 2nd. Drive data set (DDS)
P1005[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
Level
2
Level
2
Level
2
Level
2