Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
207
3.35 Faults, Alarms, Monitoring
P2100[3] Alarm number selection Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALARMS Active: first confirm QuickComm.: No Max: 65535
Selects up to 3 faults or warnings for non-default reactions.
Index:
P2100[0] : Fault Number 1
P2100[1] : Fault Number 2
P2100[2] : Fault Number 3
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0] = 5, then select the desired
reaction in P2101[0] (in this case, set P2101[0] = 3).
Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g.
overcurrent) cannot be changed from the default reactions.
P2101[3] Stop reaction value Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALARMS Active: first confirm QuickComm.: No Max: 4
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction).
This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Possible Settings:
0 No reaction, no display
1 OFF1 stop reaction
2 OFF2 stop reaction
3 OFF3 stop reaction
4 No reaction warning only
Index:
P2101[0] : Stop reaction value 1
P2101[1] : Stop reaction value 2
P2101[2] : Stop reaction value 3
Note:
- Settings 0 - 3 only are available for fault codes.
- Settings 0 and 4 only are available for warnings.
- Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103[3] BI: 1. Faults acknowledgement Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 722:2
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines first source of fault acknowledgement, e.g. keypad/DIN, etc. (depending on setting).
Index:
P2103[0] : 1st. Command data set (CDS)
P2103[1] : 2nd. Command data set (CDS)
P2103[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Level