Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
249
r2845 BO: NOT-Q RS-FF 2 Min: -
Datatype: U16 Unit: - Def: -
P-Group: TECH Max: -
Displays Not-output of RS-FlipFlop 2, inputs are defined in P2843[0], P2843[1]
Dependency:
P2801[15] is active level for the RS-FlipFlop.
P2846[2] BI: RS-FF 3 Min: 0:0
CStat: CUT Datatype: U32 Unit: - Def: 0:0
P-Group: TECH Active: first confirm QuickComm.: No Max: 4000:0
P2846[0], P2846[1] define inputs of RS-FlipFlop 3, outputs are P2847, P2848.
Index:
P2846[0] : Binector input: Set
P2846[1] : Binector input: Reset
Dependency:
P2801[16] is active level for the RS-FlipFlop.
r2847 BO: Q RS-FF 3 Min: -
Datatype: U16 Unit: - Def: -
P-Group: TECH Max: -
Displays output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1]
Dependency:
P2801[16] is active level for the RS-FlipFlop.
r2848 BO: NOT-Q RS-FF 3 Min: -
Datatype: U16 Unit: - Def: -
P-Group: TECH Max: -
Displays Not-output of RS-FlipFlop 3, inputs are defined in P2846[0], P2846[1]
Dependency:
P2801[16] is active level for the RS-FlipFlop.
Level
3
Level
3
Level
3
Level
3