Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
28 6SE6400-5BB00-0BP0
Index:
P0013[0] : 1st user parameter
P0013[1] : 2nd user parameter
P0013[2] : 3rd user parameter
P0013[3] : 4th user parameter
P0013[4] : 5th user parameter
P0013[5] : 6th user parameter
P0013[6] : 7th user parameter
P0013[7] : 8th user parameter
P0013[8] : 9th user parameter
P0013[9] : 10th user parameter
P0013[10] : 11th user parameter
P0013[11] : 12th user parameter
P0013[12] : 13th user parameter
P0013[13] : 14th user parameter
P0013[14] : 15th user parameter
P0013[15] : 16th user parameter
P0013[16] : 17th user parameter
P0013[17] : 18th user parameter
P0013[18] : 19th user parameter
P0013[19] : 20th user parameter
Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined
parameter. Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Note:
- Alternatively, set P0010 = 30 (commissioning parameter filter = factory setting) and P0970 = 1 (factory
reset) to perform a complete factory reset.
- The default values of P0011 ("lock") and P0012 ("key") are the same.
P0014[3] Store mode Min: 0
CStat: UT Datatype: U16 Unit: - Def: 0
P-Group: - Active: first confirm QuickComm.: No Max: 1
Sets the store mode for parameters ("volatile" (RAM) or "nonvolatile" (EEPROM)).
Possible Settings:
0 Volatile (RAM)
1 Nonvolatile (EEPROM)
Index:
P0014[0] : Serial interface COM link
P0014[1] : Serial interface BOP link
P0014[2] : PROFIBUS / CB
Note:
1. With the BOP the parameter will always be stored in the EEPROM.
2. P0014 itself will always be stored in the EEPROM.
3. P0014 will not be changed by performing a factory reset (P0010 = 30 and P0971 = 1).
4. P0014 can be transferred during a DOWNLOAD (P0010 = 29).
5. If "Store request via USS/CB = volatile (RAM)" and "P0014[x] = volatile (RAM)", you can make a
transfer of all parameter values into the nonvolatile memory via P0971.
6. If "Store request via USS/CB" and P0014[x] are not consistent, the setting of P14[x] = "store nonvolatile
(EEPROM)" has always higher priority.
Store request via USS/CB
EEPROM
Value of P0014[x] Result
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
RAM
RAM
RAM
RAMRAM
Level
3