Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
230 6SE6400-5BB00-0BP0
P2235[3] BI: Enable PID-MOP (UP-cmd) Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 19:13
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of UP command.
Index:
P2235[0] : 1st. Command data set (CDS)
P2235[1] : 2nd. Command data set (CDS)
P2235[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
19.D = Keypad UP button
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
P2236[3] BI: Enable PID-MOP (DOWN-cmd) Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 19:14
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of DOWN command.
Index:
P2236[0] : 1st. Command data set (CDS)
P2236[1] : 2nd. Command data set (CDS)
P2236[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E = Keypad DOWN button
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
P2240[3] Setpoint of PID-MOP Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 10.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Setpoint of the motor potentiometer.
Allows user to set a digital PID setpoint in [%].
Index:
P2240[0] : 1st. Drive data set (DDS)
P2240[1] : 2nd. Drive data set (DDS)
P2240[2] : 3rd. Drive data set (DDS)
Note:
P2240 = 100 % corresponds to 4000 hex
Level
3
Level
3
Level
2