Issue 01/06  Parameter Description 
MICROMASTER 440    Parameter List 
6SE6400-5BB00-0BP0 
153 
3.29 Control mode 
P1300[3] Control mode Min: 0 
CStat:  CT  Datatype: U16 Unit: -  Def:  0 
P-Group:  CONTROL  Active: first confirm  QuickComm.: Yes  Max:  23 
Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram 
below. 
V
n
0
f
n
V
f
V
P1325
f1
P1320
f
max
P1082
V
max
r0071
V
n
P0304
P1323
P1321
P1300 = 0 
f0
0 Hz
f2
P1322
f3
P1324
f
n
P0310
f
P1300 = 3 
P1310
P1300 = 2 
 
Possible Settings: 
0  V/f with linear characteristic 
1 V/f with FCC 
2  V/f with parabolic characteristic 
3  V/f with programmable characteristic 
4 Reserved 
5  V/f for textile applications 
6  V/f with FCC for textile applications 
19  V/f control with independent voltage setpoint 
20  Sensorless vector control 
21  Vector control with sensor 
22  Sensorless vector torque-control 
23  Vector torque-control with sensor 
Index: 
P1300[0]  :  1st. Drive data set (DDS) 
P1300[1]  :  2nd. Drive data set (DDS) 
P1300[2]  :  3rd. Drive data set (DDS) 
Dependency: 
See parameter P0205, P0500 
Caution: 
When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f 
mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in 
- sign and 
-  magnitude (with a deviation of only a few percent). 
Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23). 
 
P0400 = 1 (single channel encoder)  will only allow operation in one direction. If operation in both directions 
is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating 
Instructions of the encoder module for more information. 
Note: 
P1300 = 1 : V/f with FCC (flux current control) 
-  Maintains motor flux current for improved efficiency. 
-  If FCC is chosen, linear V/f is active at low frequencies. 
 
P1300 = 2 : V/f with a quadratic characteristic 
-  Suitable for centrifugal fans / pumps 
 
P1300 = 3 : V/f with a programmable characteristic 
-  User defined characteristic (see P1320) 
-  For synchronous motors (e.g. SIEMOSYN motors) 
 
P1300 = 5,6 : V/f for textil applications 
-  Slip compensation disabled. 
-  Imax controller modifies the output voltage only. 
-  Imax controller does not influence the output frequency. 
Level 