Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
227
P2218[3] Fixed PID setpoint mode - Bit 2 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm.: No Max: 3
BCD or direct selection Bit 2 for PID setpoint.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P2218[0] : 1st. Command data set (CDS)
P2218[1] : 2nd. Command data set (CDS)
P2218[2] : 3rd. Command data set (CDS)
P2219[3] Fixed PID setpoint mode - Bit 3 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm.: No Max: 3
BCD or direct selection Bit 3 for PID setpoint.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P2219[0] : 1st. Command data set (CDS)
P2219[1] : 2nd. Command data set (CDS)
P2219[2] : 3rd. Command data set (CDS)
P2220[3] BI: Fixed PID setp. select Bit 0 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 0
Index:
P2220[0] : 1st. Command data set (CDS)
P2220[1] : 2nd. Command data set (CDS)
P2220[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
P2221[3] BI: Fixed PID setp. select Bit 1 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 1.
Index:
P2221[0] : 1st. Command data set (CDS)
P2221[1] : 2nd. Command data set (CDS)
P2221[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
Level
3
Level
3
Level
3
Level
3