Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
223
P2201[3] Fixed PID setpoint 1 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 0.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 1
There are three options available for selection of the PID fixed setpoints:
1. Direct selection
2. Direct selection + ON command
3. Binary coded selection + ON command
1. Direct selection (P0701 - P0706 = 15):
- In this mode of operation, 1 digital input selects one PID fixed setpoint.
- If several inputs are active together, the selected setpoints are summed.
- E.g.: PID-FF1 + PID-FF2 + PID-FF3 + PID-FF4 + PID-FF5 + PID-FF6.
2. Direct selection + ON command (P0701 - P0706 = 16):
- In this mode of operation the PID fixed setpoints are combined with an ON command.
- Description as for 1), except that this type of selection issues an ON command concurrent with any
setpoint selection.
- If several inputs are active together, the selected setpoints are summed.
- E.g.: PID-FF1 + PID-FF2 + PID-FF3 + PID-FF4 + PID-FF5 + PID-FF6.
3. Binary coded selection + ON command (P0701 - P0706 = 17):
- Using this method to select the fixed PID setpoint (FF-PID) allows you to choose up to 16 different
PID setpoints.
- The setpoints are selected according to the following table:
Index:
P2201[0] : 1st. Drive data set (DDS)
P2201[1] : 2nd. Drive data set (DDS)
P2201[2] : 3rd. Drive data set (DDS)
Example:
DIN4 DIN3 DIN2 DIN1
0000
0001
001 0
0011
0 1 00
0 1 0 1
0 110
0 111
1 000
1 001
1 0 1 0
1 0 11
1100
110 1
1110
1111
Binary coded selection :
P1001
0 %
P1002
P1003
P1004
P1005
P1006
P1007
P1008
P1010
P1011
P1012
P1013
P1014
P1015
P1009
PID - FF0
PID - FF1
PID - FF2
PID - FF3
PID - FF4
PID - FF5
PID - FF6
PID - FF7
PID - FF8
PID - FF9
PID - FF10
PID - FF11
PID - FF12
PID - FF13
PID - FF14
PID - FF15
Level
2