P1094[3] Skip frequency 4 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 0.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies within
+/- P1101 (skip frequency bandwidth).
Index:
P1094[0] : 1st. Drive data set (DDS)
P1094[1] : 2nd. Drive data set (DDS)
P1094[2] : 3rd. Drive data set (DDS)
Details:
See P1091 (skip frequency 1).
P1101[3] Skip frequency bandwidth Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 2.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 10.00
Delivers frequency bandwidth to be applied to skip frequencies (in [Hz]).
Index:
P1101[0] : 1st. Drive data set (DDS)
P1101[1] : 2nd. Drive data set (DDS)
P1101[2] : 3rd. Drive data set (DDS)
Details:
See P1091 (skip frequency 1).
P1110[3] BI: Inhibit neg. freq. setpoint Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited to
the setpoint channel.
Index:
P1110[0] : 1st. Command data set (CDS)
P1110[1] : 2nd. Command data set (CDS)
P1110[2] : 3rd. Command data set (CDS)
Common Settings:
0 = Disabled
1 = Enabled
Notice:
Where
- If a min. frequency (P1080) and a negative setpoint are given, the motor is accelerated by a positive
value in relationship to the min. frequency.
- This function does not disable the "reverse command functions" (e.g. Reverse, ON left); rather, a
reverse command causes motor to run in the positive direction only, as described above.
f
t
0
1
t
f (r1170)
set
ON/OFF1
0
1
t
Reverse
f (r1078)
set
P1110 = 1
P1080
-P1080
Level
3
Level
3
Level
3