Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
87
r0752[2] Act. input of ADC [V] or [mA] Min: -
Datatype: Float Unit: - Def: -
P-Group: TERMINAL Max: -
Displays smoothed analog input value in volts before the characteristic block.
KL4
KL3
DIP switch
A
D
ADC
type
ADC
scaling
P0757
P0758
P0759
P0760
ADC
dead
zone
r0755 Pxxxx
r0752
P1000
ADC−
ADC+
r0754
P0761
P0753P0756
ADC
type
Setpoint
ADC channel
Wire
breakage
sensing
P0756 P0761
r0751
F0080
r0722
r0722.6
0
1
1.7 V
3.9 V
P0707
Pxxxx
Function
T0
P0762
Index:
r0752[0] : Analog input 1 (ADC 1)
r0752[1] : Analog input 2 (ADC 2)
P0753[2] Smooth time ADC Min: 0
CStat: CUT Datatype: U16 Unit: ms Def: 3
P-Group: TERMINAL Active: first confirm QuickComm.: No Max: 10000
Defines filter time (PT1 filter) in [ms] for analog input.
Index:
P0753[0] : Analog input 1 (ADC 1)
P0753[1] : Analog input 2 (ADC 2)
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
P0753 = 0 : No filtering
r0754[2] Act. ADC value after scaling [%] Min: -
Datatype: Float Unit: % Def: -
P-Group: TERMINAL Max: -
Shows smoothed value of analog input in [%] after scaling block.
Index:
r0754[0] : Analog input 1 (ADC 1)
r0754[1] : Analog input 2 (ADC 2)
Dependency:
P0757 to P0760 define range (ADC scaling).