Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
29
3.2 Diagnosis parameters
r0018 Firmware version Min: -
Datatype: Float Unit: - Def: -
P-Group: INVERTER Max: -
Displays version number of installed firmware.
r0019 CO/BO: BOP control word Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays status of operator panel commands.
The settings below are used as the "source" codes for keypad control when connecting to BICO input
parameters.
Bitfields:
Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit08 JOG right 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
The following functions can be "connected" to individual buttons:
- ON/OFF1,
- OFF2,
- JOG,
- REVERSE,
- INCREASE,
- DECREASE
r0020 CO: Freq. setpoint before RFG Min: -
Datatype: Float Unit: Hz Def: -
P-Group: CONTROL Max: -
Displays actual frequency setpoint (input from ramp function generator).
Motor
control
RFG
Skip
frequency
Inhibit
neg. freq.
setpoint
Reverse
Setpoint
source
r1079 r0020 r1170
P1110 P1091 P1080 P1082 P1120 P1135
. . .
IfI
r1078
JOG
r1114
r1119
r0021 CO: Act. filtered frequency 1 Min: -
Datatype: Float Unit: Hz Def: -
P-Group: CONTROL Max: -
Displays actual inverter output frequency (r0021) excluding slip compensation, resonance damping and
frequency limitation.
r0022 Act. filtered rotor speed Min: -
Datatype: Float Unit: 1/min Def: -
P-Group: CONTROL Max: -
Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of poles.
r0313
60
[Hz] r0021 [1/min] r0022 â‹…=
Note: