Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
178 6SE6400-5BB00-0BP0
r1527 CO: Lower torque limitation Min: -
Datatype: Float Unit: Nm Def: -
P-Group: CONTROL Max: -
Displays actual lower torque limitation.
Details:
See parameter r1526.
P1530[3] Motoring power limitation Min: 0.00
CStat: CUT Datatype: Float Unit: - Def: 0.12
P-Group: CONTROL Active: Immediately QuickComm.: No Max: 8000.00
Defines fixed value for the max. permissible motoring active power (motoring power limitation).
P1530
def
P1530
max
0307P3â‹…=
0307P5.2 â‹…=
Parameter P1530 limits the torque in addition to the act. frequency as displayed in the following
characteristic.
M
f
f 2
P
M
⋅π⋅
=
Power limitation (motoring, regenerative)
P1530
P1531
P1530
P1531
Index:
P1530[0] : 1st. Drive data set (DDS)
P1530[1] : 2nd. Drive data set (DDS)
P1530[2] : 3rd. Drive data set (DDS)
P1531[3] Regenerative power limitation Min: -8000.00
CStat: CUT Datatype: Float Unit: - Def: -0.12
P-Group: CONTROL Active: Immediately QuickComm.: No Max: 0.00
Enters fixed value for the max. permissible regenerative active power (regenerative power limitation).
P1531
max
P0307 3- â‹…=
P1531
def
P0307 2.5- â‹…=
Index:
P1531[0] : 1st. Drive data set (DDS)
P1531[1] : 2nd. Drive data set (DDS)
P1531[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1530.
r1536 CO: Max. trq. motoring current Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays maximum torque motoring current component.
r1537 CO: Max trq regenerative current Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays maximum torque of the regenerative current component.
Level
3
Level
2
Level
2
Level
4
Level
4