Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
212 6SE6400-5BB00-0BP0
P2159[3] Threshold frequency f_3 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 30.00
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Threshold_3 for comparing frequency to thresholds.
Tconst. speed filt
0 ... 1000 [ms]
P2153.D ( 5)
Threshold freq f_3
0.00 ... 650.00 [Hz]
P2159.D ( 30.00)
Hyst . freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
Delay time of f _3
0 ... 10000 [ms]
P2160.D (10)
Delay time of f _3
0 ... 10000 [ms]
P2160.D (10)
| f_act | <= f_3
| f_act | > f_3
T0
T0
f_act
r2198 Bit03
r2198 Bit02
| f_act | <= f_3
Threshold freq f_3
0.00 ... 650.00 [Hz]
P2159.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
0
1
{
0
1
{
| f_act | > f_3
r2169
Index:
P2159[0] : 1st. Drive data set (DDS)
P2159[1] : 2nd. Drive data set (DDS)
P2159[2] : 3rd. Drive data set (DDS)
P2160[3] Delay time of threshold freq f_3 Min: 0
CStat: CUT Datatype: U16 Unit: ms Def: 10
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for comparing frequency to threshold f_3 (P2159).
Index:
P2160[0] : 1st. Drive data set (DDS)
P2160[1] : 2nd. Drive data set (DDS)
P2160[2] : 3rd. Drive data set (DDS)
Details:
See diagram in P2159 (threshold frequency f_3)
P2161[3] Min. threshold for freq. setp. Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 3.00
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.00
Minimum threshold value for comparing frequency setpoint.
0
1
{
0
1
{
0
Setp.min.threshold
0. 00 ... 10.00 [Hz]
P2161.D (3.00)
Hyst . freq. f_hys
0.00 ... 10.00 [Hz]
P2150. D (3.00)
Hyst . freq. f _hys
0.00 ... 10.00 [Hz ]
P2150.D (3.00)
| f_set | <= P2161
| f_set | <= P2161
f_set > 0
f_set > 0
f_set
r2198 Bit04
r2198 Bit05
Index:
P2161[0] : 1st. Drive data set (DDS)
P2161[1] : 2nd. Drive data set (DDS)
P2161[2] : 3rd. Drive data set (DDS)
Level
2
Level
2
Level
2