EasyManuals Logo

Siemens MICROMASTER 440 Parameter Guide

Siemens MICROMASTER 440
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #220 background imageLoading...
Page #220 background image
Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
220 6SE6400-5BB00-0BP0
P2184[3] Belt threshold frequency 3 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 50.00
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Index:
P2184[0] : 1st. Drive data set (DDS)
P2184[1] : 2nd. Drive data set (DDS)
P2184[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2185[3] Upper torque threshold 1 Min: 0.0
CStat: CUT Datatype: Float Unit: Nm Def: 99999.0
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Upper limit threshold value 1 for comparing actual torque.
Index:
P2185[0] : 1st. Drive data set (DDS)
P2185[1] : 2nd. Drive data set (DDS)
P2185[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2186[3] Lower torque threshold 1 Min: 0.0
CStat: CUT Datatype: Float Unit: Nm Def: 0.0
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Lower limit threshold value 1 for comparing actual torque.
Index:
P2186[0] : 1st. Drive data set (DDS)
P2186[1] : 2nd. Drive data set (DDS)
P2186[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2187[3] Upper torque threshold 2 Min: 0.0
CStat: CUT Datatype: Float Unit: Nm Def: 99999.0
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Upper limit threshold value 2 for comparing actual torque.
Index:
P2187[0] : 1st. Drive data set (DDS)
P2187[1] : 2nd. Drive data set (DDS)
P2187[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2188[3] Lower torque threshold 2 Min: 0.0
CStat: CUT Datatype: Float Unit: Nm Def: 0.0
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Lower limit threshold value 2 for comparing actual torque.
Index:
P2188[0] : 1st. Drive data set (DDS)
P2188[1] : 2nd. Drive data set (DDS)
P2188[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2189[3] Upper torque threshold 3 Min: 0.0
CStat: CUT Datatype: Float Unit: Nm Def: 99999.0
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Upper limit threshold value 3 for comparing actual torque.
Index:
P2189[0] : 1st. Drive data set (DDS)
P2189[1] : 2nd. Drive data set (DDS)
P2189[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
Level
2
Level
2
Level
2
Level
2
Level
2
Level
2
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens MICROMASTER 440

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MICROMASTER 440 and is the answer not in the manual?

Siemens MICROMASTER 440 Specifications

General IconGeneral
Power Range0.12 kW to 250 kW
Output Voltage0 V to Input Voltage
Output Frequency0 Hz to 650 Hz
Control ModesVector control
Overload Capability150% for 60 seconds
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesPROFIBUS, DeviceNet, CANopen, Modbus RTU
Enclosure RatingIP20
Ambient Temperature-10°C to +50°C
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)