Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
133
P1130[3] Ramp-up initial rounding time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 0.00
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines initial rounding time in seconds as shown on the diagram below.
P1133P1132P1131P1130
t
f
f
2
f
1
t
up
t
down
where:
for
P1131) P1130(
2
1
P1120
P1082
f
-
f
12
+≥⋅
P1120
P1082
f
-
f
P1131) P1130(
2
1
t
12
up
â‹…++=
for
P1133) P1132(
2
1
P1121
P1082
f
-
f
12
+≥⋅
P1121
P1082
f
-
f
P1133) P1132(
2
1
t
12
down
â‹…++=
Index:
P1130[0] : 1st. Drive data set (DDS)
P1130[1] : 2nd. Drive data set (DDS)
P1130[2] : 3rd. Drive data set (DDS)
Note:
- If short or zero ramp times (P1120, P1121 < P1130, P1131, P1132, P1133) are set, the total ramp up
time (t_up) or ramp down time (t_down) will not depend on P1130.
- See equations above for valid conditions to calculate t_up and t_down.
- Rounding times are recommended, since they prevent an abrupt response, thus avoiding detrimental
effects on the mechanics.
- Rounding times are not recommended when analog inputs are used, since they would result in
overshoot/undershoot in the inverter response.
P1131[3] Ramp-up final rounding time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 0.00
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines rounding time at end of ramp-up as shown in P1130 (ramp-up initial rounding time).
Index:
P1131[0] : 1st. Drive data set (DDS)
P1131[1] : 2nd. Drive data set (DDS)
P1131[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1130.
P1132[3] Ramp-down initial rounding time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 0.00
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines rounding time at start of ramp-down as shown in P1130 (ramp-up initial rounding time).
Index:
P1132[0] : 1st. Drive data set (DDS)
P1132[1] : 2nd. Drive data set (DDS)
P1132[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1130.
Level
2
Level
2
Level
2