Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
48 6SE6400-5BB00-0BP0
P0290 Inverter overload reaction Min: 0
CStat: CT Datatype: U16 Unit: - Def: 2
P-Group: INVERTER Active: first confirm QuickComm.: No Max: 3
Selects reaction of inverter to an internal over-temperature.
Following physical values influence the inverter overload protection (see diagram):
- heat sink temperature
- junction temperature (IGBT temperature)
- inverter I²t
A0504
A0505
A0506
F0004
F0005
Inverter overload reaction
P0290
f_pulse
control
i_max control
(U/f)
Current control
(SLVC, VC)
r0036
r0037
Heat sink
temperature
P0292
IGBT
temperature
P0292
i
2
t
P0294
Inverter monitoring
Possible Settings:
0 Reduce output frequency
1 Trip (F0004)
2 Reduce pulse frequency and output frequency
3 Reduce pulse frequency then trip (F0004)
Notice:
P0290 = 0:
Reduction of output frequency is only effective if the load is also reduced. This is for example valid for
variable torque applications with a quadratic torque characteristic as pumps or fans.
A trip will always result, if the action taken does not sufficiently reduce internal temperature.
The pulse frequency P1800 is reduced only if higher than 2 kHz. The actual pulse frequency is displayed in
parameter r1801.
P0291[3] Inverter protection Min: 0
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: INVERTER Active: Immediately QuickComm.: No Max: 7
Bit 02 shows if phase loss dedection (input phase) of 3 phase inverters is enabled after factory reset.
Default setting of phase loss is disabled for FSA - FSC. FSD and greater it is enabled.
Bitfields:
Bit00 Reserved 0 NO 1 YES
Bit01 Reserved 0 NO 1 YES
Bit02 Phase loss detection enable 0 NO 1 YES
Index:
P0291[0] : 1st. Drive data set (DDS)
P0291[1] : 2nd. Drive data set (DDS)
P0291[2] : 3rd. Drive data set (DDS)
Details:
See P0290 (inverter overload reaction)