Parameter Description  Issue 01/06 
  MICROMASTER 440    Parameter List 
224  6SE6400-5BB00-0BP0 
Direct selection of PID-FF1 P2201 via DIN 1: 
 
P
2
2
1
6
P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1
DIN1
r2224
r0722.0
P2220
1
2,3
P2201
0
. . . .
0
. . . .
. . . .
 
Dependency: 
P2200 = 1 required in user access level 2 to enable setpoint source. 
Note: 
You may mix different types of frequencies; however, remember that they will be summed if selected 
together. 
 
P2201 = 100 % corresponds to 4000 hex 
P2202[3]  Fixed PID setpoint 2 Min: -200.00 
CStat:  CUT  Datatype: Float Unit: %  Def:  10.00 
P-Group:  TECH  Active: Immediately  QuickComm.: No  Max:  200.00 
Defines Fixed PID Setpoint 2 
Index: 
P2202[0]  :  1st. Drive data set (DDS) 
P2202[1]  :  2nd. Drive data set (DDS) 
P2202[2]  :  3rd. Drive data set (DDS) 
Details: 
See P2201 (Fixed PID Setpoint 1). 
P2203[3]  Fixed PID setpoint 3 Min: -200.00 
CStat:  CUT  Datatype: Float Unit: %  Def:  20.00 
P-Group:  TECH  Active: Immediately  QuickComm.: No  Max:  200.00 
Defines Fixed PID Setpoint 3 
Index: 
P2203[0]  :  1st. Drive data set (DDS) 
P2203[1]  :  2nd. Drive data set (DDS) 
P2203[2]  :  3rd. Drive data set (DDS) 
Details: 
See P2201 fixed PID setpoint 1 (FF-PID 1). 
P2204[3]  Fixed PID setpoint 4 Min: -200.00 
CStat:  CUT  Datatype: Float Unit: %  Def:  30.00 
P-Group:  TECH  Active: Immediately  QuickComm.: No  Max:  200.00 
Defines Fixed PID Setpoint 4 
Index: 
P2204[0]  :  1st. Drive data set (DDS) 
P2204[1]  :  2nd. Drive data set (DDS) 
P2204[2]  :  3rd. Drive data set (DDS) 
Details: 
See P2201 (Fixed PID Setpoint 1). 
P2205[3]  Fixed PID setpoint 5 Min: -200.00 
CStat:  CUT  Datatype: Float Unit: %  Def:  40.00 
P-Group:  TECH  Active: Immediately  QuickComm.: No  Max:  200.00 
Defines Fixed PID Setpoint 5 
Index: 
P2205[0]  :  1st. Drive data set (DDS) 
P2205[1]  :  2nd. Drive data set (DDS) 
P2205[2]  :  3rd. Drive data set (DDS) 
Details: 
See P2201 (Fixed PID Setpoint 1). 
Level 
2 
Level 
2 
Level 
2 
Level 
2