EasyManua.ls Logo

Siemens MICROMASTER 440 - Fixed PID Setpoint 2; Fixed PID Setpoint 3; Fixed PID Setpoint 4; Fixed PID Setpoint 5

Siemens MICROMASTER 440
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
224 6SE6400-5BB00-0BP0
Direct selection of PID-FF1 P2201 via DIN 1:
P
2
2
1
6
P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1
DIN1
r2224
r0722.0
P2220
1
2,3
P2201
0
. . . .
0
. . . .
. . . .
Dependency:
P2200 = 1 required in user access level 2 to enable setpoint source.
Note:
You may mix different types of frequencies; however, remember that they will be summed if selected
together.
P2201 = 100 % corresponds to 4000 hex
P2202[3] Fixed PID setpoint 2 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 10.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 2
Index:
P2202[0] : 1st. Drive data set (DDS)
P2202[1] : 2nd. Drive data set (DDS)
P2202[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2203[3] Fixed PID setpoint 3 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 20.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 3
Index:
P2203[0] : 1st. Drive data set (DDS)
P2203[1] : 2nd. Drive data set (DDS)
P2203[2] : 3rd. Drive data set (DDS)
Details:
See P2201 fixed PID setpoint 1 (FF-PID 1).
P2204[3] Fixed PID setpoint 4 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 30.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 4
Index:
P2204[0] : 1st. Drive data set (DDS)
P2204[1] : 2nd. Drive data set (DDS)
P2204[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2205[3] Fixed PID setpoint 5 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 40.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 5
Index:
P2205[0] : 1st. Drive data set (DDS)
P2205[1] : 2nd. Drive data set (DDS)
P2205[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
Level
2
Level
2
Level
2
Level
2
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens MICROMASTER 440

Related product manuals