P1058[3]  JOG frequency right Min: 0.00 
CStat:  CUT  Datatype: Float Unit: Hz  Def:  5.00 
P-Group:  SETPOINT  Active: Immediately  QuickComm.: No  Max:  650.00 
Jogging increases the motor frequency by small amounts. The JOG buttons uses a non-latching switch on 
one of the digital inputs to control the motor frequency. 
 
If JOG clockwise (jogging clockwise) or JOG counter-clockwise is selected, the speed is increased until the 
value, set in P1058 is reached. 
 
JOG right
f
P1058
P1059
A0923 A0923
P1060
P1060
(0)
P1055
(0)
P1056
"1"
"0"
"1"
"0"
t
t
t
P1061
DIN
BOP
USS
BOP link
USS
COM link
CB
COM link
JOG left
P1082
-P1082
P1061
 
Index: 
P1058[0]  :  1st. Drive data set (DDS) 
P1058[1]  :  2nd. Drive data set (DDS) 
P1058[2]  :  3rd. Drive data set (DDS) 
Dependency: 
P1060 and P1061 set up and down ramp times respectively for jogging. 
P1059[3]  JOG frequency left Min: 0.00 
CStat:  CUT  Datatype: Float Unit: Hz  Def:  5.00 
P-Group:  SETPOINT  Active: Immediately  QuickComm.: No  Max:  650.00 
While JOG left is selected, this parameter determines the frequency at which the inverter will run. 
Index: 
P1059[0]  :  1st. Drive data set (DDS) 
P1059[1]  :  2nd. Drive data set (DDS) 
P1059[2]  :  3rd. Drive data set (DDS) 
Dependency: 
P1060 and P1061 set up and down ramp times respectively for jogging. 