Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
213
P2162[3] Hysteresis freq. for overfreq. Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 20.00
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 650.00
Hysteresis frequency for overfrequency-detection as illustrated in the diagram below.
0
1
{
Max. frequency
0.00 ... 650.00 [Hz]
P1082.D (50.00)
Overspd. hyst.freq
0.00 ... 650.00 [Hz ]
P2162.D (20.00)
f_act > f_max
f_act
f_act > f_max
r2197 Bit06
Index:
P2162[0] : 1st. Drive data set (DDS)
P2162[1] : 2nd. Drive data set (DDS)
P2162[2] : 3rd. Drive data set (DDS)
P2163[3] Entry freq. for perm. deviation Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 3.00
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 20.00
Threshold for detecting frequency deviation from setpoint as illustrated in the diagram P2164.
Index:
P2163[0] : 1st. Drive data set (DDS)
P2163[1] : 2nd. Drive data set (DDS)
P2163[2] : 3rd. Drive data set (DDS)
P2164[3] Hysteresis frequency deviation Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 3.00
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10.00
Hysteresis frequency for detecting permitted deviation (from setpoint). This frequency controls bit 8 in status
word 1 (r0052) and bit 6 in status word 2 (r0053).
–
+
0
1
{
Entry freq . deviat
0.00 ... 20.00 [Hz]
P2163.D (3.00)
Delay_T perm. dev.
0 ... 10000 [ms]
P2165.D (10)
Hyster freq deviat
0.00 ... 10.00 [Hz ]
P2 164. D ( 3. 00)
f_act
f_act == f_set
f_set
f_act == f_set
0T
r2197 Bit07
r0052 Bit08
r0053 Bit06
Index:
P2164[0] : 1st. Drive data set (DDS)
P2164[1] : 2nd. Drive data set (DDS)
P2164[2] : 3rd. Drive data set (DDS)
P2165[3] Delay time permitted deviation Min: 0
CStat: CUT Datatype: U16 Unit: ms Def: 10
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 10000
Delay time for detecting permitted deviation of frequency from setpoint.
Index:
P2165[0] : 1st. Drive data set (DDS)
P2165[1] : 2nd. Drive data set (DDS)
P2165[2] : 3rd. Drive data set (DDS)
Details:
See diagram in P2164.
Level
2
Level
2
Level
3
Level
2