Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
77
3.9 Digital inputs
P0701[3] Function of digital input 1 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 99
Selects function of digital input 1.
DIN channel (e.g. DIN1 - PNP (P0725 = 1))
24 V
T0
&
0
1
PNP/NPN DIN
0 ... 1
P0725 (1)
0 V
24
V
Debounce time : DIN
0 ... 3
P0724 (3)
CO/BO: Bin.inp.val
r0722
r0722
.0
Kl.9
P24 (PNP)
Kl.28
0 V (NPN)
Pxxxx BI : ...
P070 1
Function
0
1
Possible Settings:
0 Digital input disabled
1 ON/OFF1
2 ON reverse /OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
25 DC brake enable
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Index:
P0701[0] : 1st. Command data set (CDS)
P0701[1] : 2nd. Command data set (CDS)
P0701[2] : 3rd. Command data set (CDS)
Dependency:
Setting 99 (enable BICO parameterization) requires
- P0700 command source or
- P0010 = 1, P3900 = 1, 2 or 3 quick commissioning or
- P0010 = 30, P0970 = 1 factory reset in order to reset.
Notice:
Setting 99 (BICO) for expert use only.
Level