Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
221
P2190[3] Lower torque threshold 3 Min: 0.0
CStat: CUT Datatype: Float Unit: Nm Def: 0.0
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 99999.0
Lower limit threshold value 3 for comparing actual torque.
Index:
P2190[0] : 1st. Drive data set (DDS)
P2190[1] : 2nd. Drive data set (DDS)
P2190[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2192[3] Time delay for belt failure Min: 0
CStat: CUT Datatype: U16 Unit: s Def: 10
P-Group: ALARMS Active: Immediately QuickComm.: No Max: 65
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events caused by transient
conditions. It is used for both methods of fault detection.
Index:
P2192[0] : 1st. Drive data set (DDS)
P2192[1] : 2nd. Drive data set (DDS)
P2192[2] : 3rd. Drive data set (DDS)
r2197 CO/BO: Monitoring word 1 Min: -
Datatype: U16 Unit: - Def: -
P-Group: ALARMS Max: -
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function.
Bitfields:
Bit00 f_act <= P1080 (f_min) 0 NO 1 YES
Bit01 f_act <= P2155 (f_1) 0 NO 1 YES
Bit02 f_act > P2155 (f_1) 0 NO 1 YES
Bit03 f_act > zero 0 NO 1 YES
Bit04 f_act >= setp. (f_set) 0 NO 1 YES
Bit05 f_act <= P2167 (f_off) 0 NO 1 YES
Bit06 f_act >= P1082 (f_max) 0 NO 1 YES
Bit07 f_act == setp. (f_set) 0 NO 1 YES
Bit08 Act. current r0068 > P2170 0 NO 1 YES
Bit09 Act. unfilt. Vdc < P2172 0 NO 1 YES
Bit10 Act. unfilt. Vdc > P2172 0 NO 1 YES
Bit11 Load missing 0 NO 1 YES
r2198 CO/BO: Monitoring word 2 Min: -
Datatype: U16 Unit: - Def: -
P-Group: ALARMS Max: -
Monitoring word 2 which indicates the state of monitor functions. Each bit represents one monitor function.
Bitfields:
Bit00 |f_act| <= P2157 (f_2) 0 NO 1 YES
Bit01 |f_act| > P2157 (f_2) 0 NO 1 YES
Bit02 |f_act| <= P2159 (f_3) 0 NO 1 YES
Bit03 |f_act| > P2159 (f_3) 0 NO 1 YES
Bit04 |f_set| < P2161 (f_min_set) 0 NO 1 YES
Bit05 f_set > 0 0 NO 1 YES
Bit06 Motor blocked 0 NO 1 YES
Bit07 Motor pulled out 0 NO 1 YES
Bit08 | I_act r0068 | > P2170 0 NO 1 YES
Bit09 | m_act | > P2174 & setpoint reached 0 NO 1 YES
Bit10 | m_act | > P2174 0 NO 1 YES
Bit11 Belt failure warning 0 NO 1 YES
Bit12 Belt failure trip 0 NO 1 YES