EasyManua.ls Logo

Siemens MICROMASTER 440 - Bi: 2. Off2; Bi: 1. Off3

Siemens MICROMASTER 440
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
104 6SE6400-5BB00-0BP0
P0845[3] BI: 2. OFF2 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 19:1
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines second source of OFF2.
The first three digits describe the parameter number of the command source and the last digit denotes the
bit setting for that parameter. If one of the digital inputs is selected for OFF2, the inverter will not run unless
the digital input is active.
Index:
P0845[0] : 1st. Command data set (CDS)
P0845[1] : 2nd. Command data set (CDS)
P0845[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0 = ON/OFF1 via BOP
Details:
See parameter P0844.
P0848[3] BI: 1. OFF3 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines first source of OFF3.
The first three digits describe the parameter number of the command source and the last digit denotes the
bit setting for that parameter. If one of the digital inputs is selected for OFF3, the inverter will not run unless
the digital input is active.
f
f max
(P1082)
f
2
0
P1135
t
down,OFF3
P1082
f
P1135
t
2
3OFF,down
â‹…=
OFF3
P2168
P2167
r0052 Bit02
Operation
Pulse
cancellation
t
t
t
P2168
f
act ,motor
f
act ,inverter
Index:
P0848[0] : 1st. Command data set (CDS)
P0848[1] : 2nd. Command data set (CDS)
P0848[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.0 = ON/OFF1 via BOP
Dependency:
Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).
Note:
- OFF3 means fast ramp-down to 0 Hz through P1135.
- OFF3 is low-active.
- Priority of all OFF commands: OFF2, OFF3, OFF1
Level
3
Level
3
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens MICROMASTER 440

Related product manuals