Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
124 6SE6400-5BB00-0BP0
P1060[3] JOG ramp-up time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 10.00
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 650.00
Sets jog ramp-up time. This is the time used while jogging is active.
f (Hz)
t (s)
f max
(P1082)
P1060
t
up
P1060
P1082
1058P
t
up
â‹…=
P1058
0
JOG
Index:
P1060[0] : 1st. Drive data set (DDS)
P1060[1] : 2nd. Drive data set (DDS)
P1060[2] : 3rd. Drive data set (DDS)
Notice:
Ramp times will be used as follows:
- P1060 / P1061 : JOG mode is active
- P1120 / P1121 : Normal mode (ON/OFF) is active
- P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
P1061[3] JOG ramp-down time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 10.00
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 650.00
Sets ramp-down time. This is the time used while jogging is active.
f (Hz)
t (s)
f max
(P1082)
P1061
P1082
1058P
t
down
â‹…=
P1061
t
down
JOG
P1058
0
Index:
P1061[0] : 1st. Drive data set (DDS)
P1061[1] : 2nd. Drive data set (DDS)
P1061[2] : 3rd. Drive data set (DDS)
Notice:
Ramp times will be used as follows:
- P1060 / P1061 : JOG mode is active
- P1120 / P1121 : Normal mode (ON/OFF) is active
- P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
Level
2
Level
2