Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
33
P0040 Reset energy consumption meter Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: INVERTER Active: first confirm QuickComm.: No Max: 1
Resets value of parameter r0039 (energy consumption meter) to zero.
Possible Settings:
0 No reset
1 Reset r0039 to 0
Dependency:
No reset until "P" is pressed.
r0050 CO: Active command data set Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays currently selected and active command data set (CDS).
Possible Settings:
0 1st. Command data set (CDS)
1 2nd. Command data set (CDS)
2 3rd. Command data set (CDS)
Details:
See parameter P0810.
r0051[2] CO: Active drive data set (DDS) Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays currently selected and active drive data set (DDS).
Possible Settings:
0 1st. Drive data set (DDS)
1 2nd. Drive data set (DDS)
2 3rd. Drive data set (DDS)
Index:
r0051[0] : Selected drive data set
r0051[1] : Active drive data set
Details:
See parameter P0820.