Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
82 6SE6400-5BB00-0BP0
Index:
P0719[0] : 1st. Command data set (CDS)
P0719[1] : 2nd. Command data set (CDS)
P0719[2] : 3rd. Command data set (CDS)
Note:
Using parameter P0719, it is possible to select the command or setpoint sources without changing the BICO
connections (this is contrary to P0700 / P1000). However, it is not possible to change the complete
connection table (refer to P0700 and P1000). Using P0719, depending on the value, only the BICO
parameters listed in the following table are internally overwritten - this means that these BICO parameters
are inactive.
Command source:
P0840 X
− − − −
P0844 X
− − − −
P0848 X X
− − −
P0852 X X
− − −
P1035 X
− − −−
P1036 X X
− − −
P1055 X
− − −−
P1056 X X
− − −
P1113 X
− − −−
P1140 X X
− − −
P1141 X X
− − −
P1142 X X
− − −
P1143 X X
− − −
P0719 =
40 ... 490 ... 9 10 ... 19 50 ... 59 60 ... 69
all other values
P1070 X
−
P0719 =
0, 10, 20, 40, 50, 60
BICO parameter active
Setpoint source:
X =
BICO parameter inactive
−
=
BICO connections made previously remain unchanged.
r0720 Number of digital inputs Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays number of digital inputs.
r0722 CO/BO: Binary input values Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays status of digital inputs.
Bitfields:
Bit00 Digital input 1 0 OFF 1 ON
Bit01 Digital input 2 0 OFF 1 ON
Bit02 Digital input 3 0 OFF 1 ON
Bit03 Digital input 4 0 OFF 1 ON
Bit04 Digital input 5 0 OFF 1 ON
Bit05 Digital input 6 0 OFF 1 ON
Bit06 Digital input 7 (via ADC 1) 0 OFF 1 ON
Bit07 Digital input 8 (via ADC 2) 0 OFF 1 ON
Note:
Segment is lit when signal is active.
Level
3
Level
2