134 6SE6400-5BB00-0BP0
P1133[3] Ramp-down final rounding time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 0.00
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 40.00
Defines rounding time at end of ramp-down as shown in P1130 (ramp-up initial rounding time).
Index:
P1133[0] : 1st. Drive data set (DDS)
P1133[1] : 2nd. Drive data set (DDS)
P1133[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1130.
P1134[3] Rounding type Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 1
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g.
new setpoint, OFF1, OFF3, REV).
This smoothing is applied, if the motor is ramped-up or ramped-down and
- P1134 = 0,
- P1132 > 0, P1133 > 0 and
- the setpoint is not yet reached.
f
OFF1
ON
t
Setpoint reached
f
Set
t
f
P1132 > 0, P1133 > 0
P1132
Setpoint reached
Setpoint not reached
f
Set
t
Setpoint not reached
P1134 = 0
P1134 = 1
P1133 P1133P1132
P1132 P1133 P1133
Possible Settings:
0 Continuous smoothing
1 Discontinuous smoothing
Index:
P1134[0] : 1st. Drive data set (DDS)
P1134[1] : 2nd. Drive data set (DDS)
P1134[2] : 3rd. Drive data set (DDS)
Dependency:
No effect until P1132 (Ramp-down initial rounding time) or P1133 (Ramp-down final rounding time) > 0 s.
Level
2
Level
2