Parameter Description  Issue 01/06 
  MICROMASTER 440    Parameter List 
166  6SE6400-5BB00-0BP0 
3.29.1.4 Soft starting 
P1350[3] Voltage soft start Min: 0 
CStat:  CUT  Datatype: U16 Unit: -  Def:  0 
P-Group:  CONTROL  Active: first confirm  QuickComm.: No  Max:  1 
Selecting the soft starting function. 
 
With soft starting, the flux in the motor is established with some delay. This ensures that the motor only 
rotates in the required direction of rotation even with existing residual magnetism. When activated, at 
powered-on, the output voltage is ramped-up to the value of the characteristic voltage within the 
magnetizing time P0346. 
 
f
V
t
1
P0346
P1350 P0346
V/f characteristic
Softstart
V
f
f
 
Possible Settings: 
0 OFF 
1 ON 
Index: 
P1350[0]  :  1st. Drive data set (DDS) 
P1350[1]  :  2nd. Drive data set (DDS) 
P1350[2]  :  3rd. Drive data set (DDS) 
Note: 
The settings for this parameter bring benefits and drawbacks: 
-  P1350 = 0: (jump to boost voltage) 
  Benefit:  flux is built up quickly 
  Drawback: motor may move 
-  P1350 = 1: (smooth voltage build-up) 
  Benefit:  motor less likely to move 
  Drawback: flux build-up takes longer 
 
Level 
3