Parameter Description  Issue 01/06 
  MICROMASTER 440    Parameter List 
258  6SE6400-5BB00-0BP0 
P3980  Commissioning command selection Min: 0 
CStat:  T  Datatype: U16 Unit: -  Def:  0 
P-Group:  -  Active: first confirm  QuickComm.: No  Max:  67 
Toggles command and setpoint sources between freely programmable BICO parameters and fixed 
command/setpoint profiles for commissioning. 
 
The command and setpoint sources can be changed independently. The tens digit selects the command 
source, the ones digit the setpoint source. 
Possible Settings: 
0  Cmd = BICO parameter   Setpoint = BICO parameter 
1  Cmd = BICO parameter   Setpoint = MOP setpoint 
2  Cmd = BICO parameter   Setpoint = Analog setpoint 
3  Cmd = BICO parameter   Setpoint = Fixed frequency 
4  Cmd = BICO parameter   Setpoint = USS on BOP link 
5  Cmd = BICO parameter   Setpoint = USS on COM link 
6  Cmd = BICO parameter   Setpoint = CB  on COM link 
7  Cmd = BICO parameter   Setpoint = Analog 2 setp 
10  Cmd = BOP          Setpoint = BICO parameter 
11  Cmd = BOP          Setpoint = MOP setpoint 
12  Cmd = BOP          Setpoint = Analog setpoint 
13  Cmd = BOP          Setpoint = Fixed frequency 
15  Cmd = BOP          Setpoint = USS on COM link 
16  Cmd = BOP          Setpoint = CB  on COM link 
17  Cmd = BOP          Setpoint = Analog 2 setp 
40  Cmd = USS on BOP link  Setpoint = BICO parameter 
41  Cmd = USS on BOP link  Setpoint = MOP setpoint 
42  Cmd = USS on BOP link  Setpoint = Analog setpoint 
43  Cmd = USS on BOP link  Setpoint = Fixed frequency 
44  Cmd = USS on BOP link  Setpoint = USS on BOP link 
45  Cmd = USS on BOP link  Setpoint = USS on COM link 
46  Cmd = USS on BOP link  Setpoint = CB  on COM link 
47  Cmd = USS on BOP link  Setpoint = Analog 2 setp 
50  Cmd = USS on COM link  Setpoint = BICO parameter 
51  Cmd = USS on COM link  Setpoint = MOP setpoint 
52  Cmd = USS on COM link  Setpoint = Analog setpoint 
53  Cmd = USS on COM link  Setpoint = Fixed frequency 
54  Cmd = USS on COM link  Setpoint = USS on BOP link 
55  Cmd = USS on COM link  Setpoint = USS on COM link 
57  Cmd = USS on COM link  Setpoint = Analog 2 setp 
60  Cmd = CB  on COM link  Setpoint = BICO parameter 
61  Cmd = CB  on COM link  Setpoint = MOP setpoint 
62  Cmd = CB  on COM link  Setpoint = Analog setpoint 
63  Cmd = CB  on COM link  Setpoint = Fixed frequency 
64  Cmd = CB  on COM link  Setpoint = USS on BOP link 
66  Cmd = CB  on COM link  Setpoint = CB  on COM link 
67  Cmd = CB  on COM link  Setpoint = Analog 2 setp 
P3981 Reset active fault Min: 0 
CStat:  CT  Datatype: U16 Unit: -  Def:  0 
P-Group:  ALARMS  Active: first confirm  QuickComm.: No  Max:  1 
Resets active faults when changed from 0 to 1. 
Possible Settings: 
0  No fault reset 
1 Reset fault 
Note: 
Automatically reset to 0. 
Details: 
See r0947 (last fault code) 
r3986[2]  Number of parameters Min: - 
  Datatype: U16 Unit: -  Def:  - 
P-Group:  -     Max:  - 
Number of parameters on the drive 
Index: 
r3986[0]  :  Read only 
r3986[1]  :  Read & write 
 
 
 
 