Issue 01/06  Function Diagrams 
MICROMASTER 440    Parameter List 
6SE6400-5BB00-0BP0 
271 
- 2700 -
Function diagram
87654321
2700_CBonCOM.vsd
External Interfaces
MICROMASTER 440
16.01.2006     V2.1
CB on COM link, Receiving
PKW
PZD
1
[0]
r2050
[1]
[2]
[3]
2
3
4
5
6
7
[4]
[5]
[6]
[7]
CB tel. off time
0 ... 65535  [ms]
P2040 (20)
BO: CtrlWd1 <- CB
r2090
BO: CtrlWd2 <- CB
r2091
PZD
PKW
7 6 5 4 3 2 1
Receive telegram
RxD
Receive
CB
configuration
Change par. via
0 ... 15
P0927 (15)
CB parameter
0 ... 65535
P2041 [5] (0)
Bit0 = 1
Note:
Bit 10 must be set in the first PZD word of the
telegram received via USS so that the converter
will accept the process data as
being valid. For this reason, the control
word 1 must be transferred to the converter
in the first PZD word.
Bit00   ON/OFF1
Bit01   OFF2: Electrical stop
Bit02   OFF3: Fast stop
Bit03   Pulse enable
Bit04   RFG enable
Bit05   RFG start
Bit06   Setpoint enable
Bit07   Fault acknowledge
Bit08   JOG right
Bit09   JOG left
Bit10   Control from PLC
Bit11   Reverse (setpoint inversion)
Bit13   Motor potentiometer MOP up
Bit14   Motor potentiometer MOP down
Bit15   CDS Bit 0 (Local/Remote)
Bit00   Fixed frequency Bit 0
Bit01   Fixed frequency Bit 1
Bit02   Fixed frequency Bit 2
Bit03   Fixed frequency Bit 3
Bit04   Drive data set (DDS) Bit 0
Bit05   Drive data set (DDS) Bit 1
Bit08   PID enabled
Bit09   DC brake enabled
Bit11   Droop
Bit12   Torque control
Bit13   External fault 1
Bit15   Command data set (CDS) Bit 1
CB-Frame
CB-Frame
0
0