Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
116 6SE6400-5BB00-0BP0
P1012[3] Fixed frequency 12 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 55.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 12.
Index:
P1012[0] : 1st. Drive data set (DDS)
P1012[1] : 2nd. Drive data set (DDS)
P1012[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1013[3] Fixed frequency 13 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 60.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 13.
Index:
P1013[0] : 1st. Drive data set (DDS)
P1013[1] : 2nd. Drive data set (DDS)
P1013[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1014[3] Fixed frequency 14 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 65.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 14.
Index:
P1014[0] : 1st. Drive data set (DDS)
P1014[1] : 2nd. Drive data set (DDS)
P1014[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1015[3] Fixed frequency 15 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 65.00
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 650.00
Defines fixed frequency setpoint 15.
Index:
P1015[0] : 1st. Drive data set (DDS)
P1015[1] : 2nd. Drive data set (DDS)
P1015[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1016[3] Fixed frequency mode - Bit 0 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the mode of selection
Bit 0.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P1016[0] : 1st. Command data set (CDS)
P1016[1] : 2nd. Command data set (CDS)
P1016[2] : 3rd. Command data set (CDS)
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.