Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
40 6SE6400-5BB00-0BP0
r0075 CO: Current setpoint Isd Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays setpoint of flux generating current component.
Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value
zero.
r0076 CO: Act. current Isd Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays flux generating current component.
Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value
zero.
r0077 CO: Current setpoint Isq Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays setpoint for component of torque generating current.
Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value
zero.
r0078 CO: Act. current Isq Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays component of torque generating current.
r0079 CO: Torque setpoint (total) Min: -
Datatype: Float Unit: Nm Def: -
P-Group: CONTROL Max: -
Displays total torque setpoint.
Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value
zero.
r0080 CO: Act. torque Min: -
Datatype: Float Unit: Nm Def: -
P-Group: CONTROL Max: -
Displays actual torque. Output value will be zero at low frequencies when current injection is active (r1751.5
= 1).
r0084 CO: Act. air gap flux Min: -
Datatype: Float Unit: % Def: -
P-Group: CONTROL Max: -
Displays air gap flux in [%] relative to the rated motor flux.
r0086 CO: Act. active current Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays active (real part) of motor current.
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0090 CO: Act. rotor angle Min: -
Datatype: Float Unit: ° Def: -
P-Group: CONTROL Max: -
Indicates the current angle of the rotor. This function is not available on single input channel encoders.
Level
3
Level
3
Level
3
Level
3
Level
3
Level
4
Level
4
Level
3
Level
2