Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
84 6SE6400-5BB00-0BP0
3.10 Digital outputs
r0730 Number of digital outputs Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays number of digital outputs (relays).
P0731[3] BI: Function of digital output 1 Min: 0:0
CStat: CUT Datatype: U32 Unit: - Def: 52:3
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines source of digital output 1.
(52:3)
BI: Fct. of DOUT 1
P0731.C
-1
0
1
Invert DOUTs
0 ... 7
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.20
Kl.18
.0
Function
xxxx .y
rxxxx. y
P0731 = xxxx.y
DOUT channel
Relay :
DC 30 V / 5 A
AC 250 V / 2 A
Kl.28
Kl.9
int. 24 V
max. 100 mA
NO
COM
NC
Kl.19
or
max. load capability
max. opening / closing time
5 / 10 ms
Index:
P0731[0] : 1st. Command data set (CDS)
P0731[1] : 2nd. Command data set (CDS)
P0731[2] : 3rd. Command data set (CDS)
Common Settings:
52.0 Drive ready 0 Closed
52.1 Drive ready to run 0 Closed
52.2 Drive running 0 Closed
52.3 Drive fault active 0 Closed
52.4 OFF2 active 1 Closed
52.5 OFF3 active 1 Closed
52.6 Switch on inhibit active 0 Closed
52.7 Drive warning active 0 Closed
52.8 Deviation setpoint/actual value 1 Closed
52.9 PZD control (Process Data Control) 0 Closed
52.A Maximum frequency reached 0 Closed
52.B Warning: Motor current limit 1 Closed
52.C Motor holding brake (MHB) active 0 Closed
52.D Motor overload 1 Closed
52.E Motor running direction right 0 Closed
52.F Inverter overload 1 Closed
53.0 DC brake active 0 Closed
53.1 Act. freq. f_act > P2167 (f_off) 0 Closed
53.2 Act. freq. f_act <= P1080 (f_min) 0 Closed
53.3 Act. current r0027 > P2170 0 Closed
53.4 Act. freq. f_act > P2155 (f_1) 0 Closed
53.5 Act. freq. f_act <= P2155 (f_1) 0 Closed
53.6 Act. freq. f_act >= setpoint 0 Closed
53.7 Act. Vdc r0026 < P2172 0 Closed
53.8 Act. Vdc r0026 > P2172 0 Closed
53.A PID output r2294 == P2292 (PID_min) 0 Closed
53.B PID output r2294 == P2291 (PID_max) 0 Closed
Details:
Display functions ==> see parameter r0052, r0053
Motor holding brake ==> see parameter P1215
DC brake ==> see parameter P1232, P1233
Level
3
Level
2