Issue 01/06 Function Diagrams
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
297
**) The speed integrator doesn't work in
the range of the observer model
*) settable via P1500
- 7200 -
Function diagram
87654321
7200.vsd
Vector Control
MICROMASTER 440
16.01.2006 V2.1
Overview of Torque Control without Encoder:
2
CI: Add. trq. setp
(0:0)
P1511.C
CI: Torque setp.
(0:0)
P1503.C
r1508
CO: Torque setp. [Nm]
Inertia [kg*m^2]
0.00010 ... 1000.00000
P0341.D (0.00180)
Scal acc. trq ctrl
0.0 ... 400.0 [%]
P1499.D (100.0)
r0063
CO: Act. frequency [Hz]
*)
*)
CO: Upper trq. lim
-99999.00 ... 99999.00 [Nm]
P1520.D (5.13)
CO: Lower trq. lim
-99999.00 ... 99999.00 [Nm]
P1521.D (-5.13)
CI: Upper trq. lim
(1520:0)
P1522.C
CI: Lower trq. lim
(1521:0)
P1523.C
Torque limitation
r1538
CO:Total up TrqLim [Nm]
r0079
CO: Total trq setp [Nm]
x
y
Efficiency optimiz
0 ... 100 [%]
P1580.D (0)
CO: Fval flux setp
50.0 ... 200.0 [%]
P1570.D (107.0)
r1539
CO:Total lw TrqLim [Nm]
Motor ovl fact [%]
10.0 ... 400.0 [%]
P0640.D (150.0)
Motoring power lim
0.00 ... 8000.00
P1530.D (0.12)
Regener. power lim
-8000.00 ... 0.00
P1531.D (-0.12)
Cont. torque boost
0.0 ... 200.0 [%]
P1610.D (50.0)
Acc trq boost SLVC
0.0 ... 200.0 [%]
P1611.D (0.0)
30 ms
Sheet 7700
Torque/current limit
Flux setpoint
Sheet 7900
r0071
CO: Max. outp.volt [V]
Sheet 7800
P1300 = 22 or P1300 = 20 and P1501 = 1
Current control,
Observer model
r1515
CO: Add. trq. setp [Nm]
r0067
CO: Outp cur limit [A]
Tot/mot inert.rat.
1.000 ... 400.000
P0342.D (1.000)
Max. frequency
0.00 ... 650.00 [Hz]
P1082.D (50.00)
Max. frequency
0.00 ... 650.00 [Hz]
P1082.D (50.00)
–
Asyc.
Mot. 3~
4
r0030
CO: Act. cur. Isq [A]
Gain current ctrl.
0.00 ... 5.00
P1715.D (0.25)
Int.time cur. ctrl
1.0 ... 50.0 [ms]
P1717.D (4.1)
Kp Tn
–
–
r0029
CO: Act. cur. Isd [A]
Voltage
6
Pulse frequency
2 ... 16 [kHz]
P1800 (4)
r0068
CO: Output current [A]
5
*)
*)
r0070
CO: Act. Vdc [V]
r0072
CO: Act. outp.volt [V]
+
+
r0065
CO: Slip frequency [%]
r0066
CO: Act. outp freq [Hz]
Kp n-adapt. (SLVC)
0.0 ... 2.5
P1764.D (0.2)
Tn n-adapt. (SLVC)
1.0 ... 200.0 [ms]
P1767.D (4.0)
Observer
model
Current
model
3
*)
*)
Modulator
Scal. low trq. lim
-400.0 ... 400.0 [%]
P1525.D (100.0)
www . ElectricalPartManuals . com