Faults and Alarms Issue 01/06
MICROMASTER 440 Parameter List
312 6SE6400-5BB00-0BP0
F0054 Incorrect I/O module STOP II
Quit
Refer to F0001
Cause
- incorrect I/O module inserted.
- no ID of the I/O module found, no data.
Diagnosis & Remedy
Please check the following:
- check I/O data, if required repeat the operation
- the installation of the I/O module in the inverter if required, replace the I/O module
F0060 Asic time slice overflow STOP II
Quit
Refer to F0001
Cause
- internal communications failure/error
Diagnosis & Remedy
- if the error still occurs, replace the inverter.
- contact customer service!
F0070 CB setpoint fault STOP II
Quit
Refer to F0001
Cause
- no setpoints received via the communications bus during the telegram failure time.
Diagnosis & Remedy
- check the communications module (CB) and communications partner.
F0071 USS(BOP link) setpoint fault STOP II
Quit
Refer to F0001
Cause
- no setpoint was received via the USS during the telegram off time
Diagnosis & Remedy
- check USS master
F0072 USS(COMM link) setpoint fault STOP II
Quit
Refer to F0001
Cause
- no setpoints received via the USS during the telegram off time
Diagnosis & Remedy
- check USS master
F0080 ADC input signal lost STOP II
Quit
Refer to F0001
Cause
- wire breakage
- signal outside the limit values
F0085 External fault STOP II
Quit
Refer to F0001
Cause
- external fault as a result of command input via terminals.
Diagnosis & Remedy
- inhibit terminal input to initiate fault.