Parameter Description  Issue 01/06 
  MICROMASTER 440    Parameter List 
92  6SE6400-5BB00-0BP0 
ASPmax
100 %
10 V
20 mA
 V
 mA
x
100%
%
P0760
P0758
P0757
P0759
ASPmin
P0761
4000 h 
P0761 > 0  and  P0758 < 0 < P0760
 
 
The below example produces a -10 to +10 V analog input (-50 to +50 Hz) with center zero and a "holding 
point" 0.2 V wide (0.1 V to each side of center). 
 
ASPmax
100 %
10 V
 V
x
100%
%
P0760
P0758
P0757
P0759
ASPmin
-10 V
P0761
4000 h 
P0756 = 4  and  P0761 > 0  and  P0758 < 0 < P0760
 
Note: 
P0761[x] = 0 : No deadband active. 
 
Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC 
scaling) are positive or negative respectively. However, deadband is active in both directions from point of 
intersection (x axis with ADC scaling curve), if sign of P0758 and P0760 are opposite. 
 
Min. frequency P1080 should be zero when using center zero setup. There is no hysteresis at the end of the 
deadband. 
P0762[2]  Delay for loss of signal action Min: 0 
CStat:  CUT  Datatype: U16 Unit: ms  Def:  10 
P-Group:  TERMINAL  Active: Immediately  QuickComm.: No  Max:  10000 
Defines time delay between loss of analog setpoint and appearance of fault code F0080. 
Index: 
P0762[0]  :  Analog input 1 (ADC 1) 
P0762[1]  :  Analog input 2 (ADC 2) 
Note: 
Expert users can choose the desired reaction to F0080 (default is OFF2). 
 
Level 
3